Single-Phase Submersible Motor Cable Limits (75°C Copper)

Motor HP Volts FLA 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG Breaker
0.5 HP 115V 9.8A 100 ft 160 ft 250 ft 390 ft 620 ft 960 ft 20A
0.5 HP 230V 4.9A 400 ft 650 ft 1020 ft 1610 ft 2510 ft 3880 ft 15A
0.75 HP 230V 6.2A 300 ft 480 ft 760 ft 1200 ft 1870 ft 2890 ft 15A
1 HP 230V 8.1A 250 ft 400 ft 630 ft 990 ft 1540 ft 2380 ft 20A
1.5 HP 230V 10.4A 190 ft 310 ft 480 ft 770 ft 1200 ft 1870 ft 25A
2 HP 230V 12.5A — 250 ft 390 ft 620 ft 970 ft 1510 ft 30A
3 HP 230V 17A — — 190 ft 300 ft 470 ft 750 ft 40A
5 HP 230V 27.5A — — 110 ft 180 ft 280 ft 450 ft 60A
7.5 HP 230V 36A — — — 140 ft 220 ft 350 ft 80A
10 HP 230V 48A — — — — 160 ft 260 ft 100A

Three-Phase Submersible Motor Cable Limits (230V & 460V)

For commercial farms, agricultural irrigation, and municipal wells operating on 3-phase power:

Motor HP 3-Phase Voltage 14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG
1.5 HP 230V 3-Phase 310 ft 490 ft 770 ft 1,210 ft 1,890 ft 2,950 ft
2.0 HP 230V 3-Phase 240 ft 390 ft 610 ft 970 ft 1,520 ft 2,370 ft
3.0 HP 230V 3-Phase 180 ft 290 ft 460 ft 730 ft 1,140 ft 1,780 ft
5.0 HP 230V 3-Phase — 170 ft 280 ft 440 ft 690 ft 1,080 ft
5.0 HP 460V 3-Phase 550 ft 880 ft 1,390 ft 2,190 ft 3,450 ft 5,360 ft

National Electrical Code (NEC) Burial & Installation Rules

NEC 300.5 Underground Trench Depth: Direct-burial UF cable requires a minimum depth of 24 inches of earth cover. Cable installed in Schedule 40 or 80 rigid nonmetallic conduit (PVC) requires 18 inches of cover.
Ambient Temperature Derating (NEC 310.15): While submerged cable in cold well water operates efficiently, above-ground surface conduit exposed to direct sunlight on exterior walls in ambient temperatures exceeding 104°F (40°C) must apply a 0.82 to 0.88 ampacity correction factor.